Input and output redundancy.
Hot swap.
High input/output isolation: 3000Vrms.
Stadard modules CRS-240 series.
Module fail alarm.
Standard 3U sub-rack.
Modular DC/DC converter consisting of a set of up to 8
modules of 280W installed in 19" subrack internally
connected in redundant mode. This allows to provide 2240W without
redundancy, 1960W with N+1 redundancy, 1680W with redundancy
N+2 etc. The equipment has got 2 input lines that feed to 2
groups of up to 4 modules. This allow to have a system with
line redundancy up to 1120W. Each converter has got a relay
that signalizes the output failure. All relays are conected
in series so that in two Terminals is detected the failure of
any module.
STANDARD
MODELS CHART
A: CC/CC Modules (+
front panel + test points)
Output
Input
48Vin (36...60V)
110Vin (77...144V)
12V
NP-9179 (240W)
NP-9182 (280W)
24V
NP-9180 (280W)
NP-9183 (280W)
48V
NP-9181 (280W)
NP-9184 (280W)
B: Subrack + Backpanel
Output
Back connection option
12
Vout.
NP-9176
NP-9176 R
24
Vout.
NP-9177
NP-9177 R
48
Vout.
NP-9178
NP-9178 R
CONFIGURATIONS
DATA SHEET
ACCESORIES 0903378: blind front panel (for not used slots)
(fixing screws included).
ORDERING INFORMATION, Example:
A
48V input voltage DC converter and 24V (2240W) output: 1 x NP-9177 + 8 x NP-9180